Back to Search Start Over

A Clarke-Wavelet-Based Time-Domain Power Transformer Differential Protection.

Authors :
Medeiros, Rodrigo Prado
Bezerra Costa, Flavio
Melo Silva, Kleber
Muro, Jose de Jesus Chavez
Junior, Jose Raimundo Lima
Popov, Marjan
Source :
IEEE Transactions on Power Delivery; Feb2022, Vol. 37 Issue 1, p317-328, 12p
Publication Year :
2022

Abstract

Phasor-based differential protection is widely used as the main protection function of the power transformer due to its reliability and ability to discriminate internal from external faults and inrush currents. However, these methods present some delays due to phasor convergence during the fault occurrence and can fail during challenging situations, such as transformer energizations with low second-harmonic content and turn-to-turn and turn-to-ground internal faults. This paper proposes a novel time-domain power transformer differential protection based on Clarke and wavelet transforms with only one differential unit and with automatic setting to be used in any power transformer. Considering both actual and simulation data, the performance validation reveals that the proposed method is efficient, ultra-fast, simple, and independent of the fundamental and harmonic components of the differential current. The method was also implemented in a real-time digital simulator to demonstrate its practical feasibility. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858977
Volume :
37
Issue :
1
Database :
Complementary Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
154862040
Full Text :
https://doi.org/10.1109/TPWRD.2021.3059732