Back to Search Start Over

AC Loss Measurement of Bifilarly Wound Magnet Using Coated Conductor.

Authors :
Ki Sung Chang
Seong Eun Yang
Dae Hee Jang
Dong Keun Park
Min Cheol Ahn
Kideok Sim
Hyoungku Kang
Bok-Yeol Seok
Tae Kuk Ko
Source :
IEEE Transactions on Applied Superconductivity; Jun2007 Part 2 of 3, Vol. 17 Issue 2, p1883-1886, 4p, 1 Black and White Photograph, 3 Diagrams, 2 Charts, 1 Graph
Publication Year :
2007

Abstract

Recently, the resistive superconducting fault current limiter (SFCL) using YBCO coated conductor (CC) has been developed in many countries. Since CC has many advantages such as high n-value and high Jc compared with BSCCO tape, CC is useful to develop the resistive SFCL. The important thing for the operation of the SFCL is to reduce the AC loss like transport current loss and magnetization loss. Although the bifilarly wound magnet is a non-inductive coil, the transport current loss will certainly be produced by self-field when the AC current flows through the CC tape. A measurement of AC loss should be essential for the commercialization of the SFCL. In this paper, the transport current loss of the bifilar magnet using CC is measured by the electric method and the calorimetric method and compared with Norris equation because inductance of the bifilarly wound magnet is very small. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
10518223
Volume :
17
Issue :
2
Database :
Complementary Index
Journal :
IEEE Transactions on Applied Superconductivity
Publication Type :
Academic Journal
Accession number :
26343535
Full Text :
https://doi.org/10.1109/TASC.2007.898357