Back to Search Start Over

A 6.6-kV transformerless cascade PWM STATCOM. Experimental verification by a three-phase 200-V, 10-kVa laboratory system.

Authors :
Yoshii, Tsurugi
Inoue, Shigenori
Akagi, Hirofumi
Source :
Electrical Engineering in Japan; Jan2010, Vol. 170 Issue 1, p55-64, 10p, 8 Diagrams, 2 Charts, 10 Graphs
Publication Year :
2010

Abstract

This paper deals with a 6.6-kV transformerless STATCOM cascading multiple single-phase H-bridge PWM converters in each phase. The AC voltage of the STATCOM is almost sinusoidal, so that it requires no harmonic filter. Each converter is equipped with a capacitor and a voltage sensor on the DC side, which are electrically isolated from each other. The STATCOM has the capability of self-starting and voltage-balancing without any external power supply or equipment. Experiments using a three-phase 200-V, 10-kVA laboratory system, along with computer simulations, are carried out to confirm the viability and effectiveness of the STATCOM. © 2009 Wiley Periodicals, Inc. Electr Eng Jpn, 170(1): 55–64, 2010; Published online in Wiley InterScience (<URL>www.interscience.wiley. com</URL>). DOI 10.1002/eej.20822 [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
04247760
Volume :
170
Issue :
1
Database :
Complementary Index
Journal :
Electrical Engineering in Japan
Publication Type :
Academic Journal
Accession number :
44435592