Back to Search Start Over

Power Loss Comparison of Single- and Two-Stage Grid-Connected Photovoltaic Systems.

Authors :
Wu, Tsai-Fu
Chang, Chih-Hao
Lin, Li-Chiun
Kuo, Chia-Ling
Source :
IEEE Transactions on Energy Conversion; Jun2011, Vol. 26 Issue 2, p707-715, 9p
Publication Year :
2011

Abstract

This paper presents power loss comparison of single- and two-stage grid-connected photovoltaic (PV) systems based on the loss factors of double line-frequency voltage ripple (DLFVR), fast irradiance variation + DLFVR, fast dc load variation + DLFVR, limited operating voltage range + DLFVR, and overall loss factor combination. These loss factors will result in power deviation from the maximum power points. In this paper, both single-stage and two-stage grid-connected PV systems are considered. All of the effects on a two-stage system are insignificant due to an additional maximum power point tracker, but the tracker will reduce the system efficiency typically about 2.5%. The power loss caused by these loss factors in a single-stage grid-connected PV system is also around 2.5%; that is, a single-stage system has the merits of saving components and reducing cost, and does not penalize overall system efficiency under certain operating voltage ranges. Simulation results with the MATLAB software package and experimental results have confirmed the analysis. [ABSTRACT FROM PUBLISHER]

Details

Language :
English
ISSN :
08858969
Volume :
26
Issue :
2
Database :
Complementary Index
Journal :
IEEE Transactions on Energy Conversion
Publication Type :
Academic Journal
Accession number :
60832031
Full Text :
https://doi.org/10.1109/TEC.2011.2123897