Back to Search Start Over

Type-III Wind Power Plant Harmonic Emissions: Field Measurements and Aggregation Guidelines for Adequate Representation of Harmonics.

Authors :
Larose, Christian
Gagnon, Richard
Prud'Homme, Pascal
Fecteau, Martin
Asmine, Mohamed
Source :
IEEE Transactions on Sustainable Energy; Jul2013, Vol. 4 Issue 3, p797-804, 8p
Publication Year :
2013

Abstract

<?Pub Dtl?>Large wind power plants (WPPs) based on variable speed turbines produce harmonics and interharmonics of voltage and current. This paper presents some generic guidelines about resulting harmonics and interharmonics at the high voltage point of interconnection (POI) of a type-III WPP. These guidelines are supported by both field measurements and time-domain electromagnetic transient (EMT) simulations. Specific focus is placed on how these harmonics and interharmonics can be represented in EMT simulation using detailed and aggregated models of a WPP. First, a theoretical explanation of the origin of all frequencies produced by a type-III wind generator (WG) is presented. The results of field measurements from a large WPP are then reported and analyzed confirming the theory. Subsequently, the field measurements are compared to simulation results of a detailed EMT model of the entire WPP and differences are explained. Finally, aggregated models of the same WPP are established and the accuracy of these aggregated models is discussed in light of the specific need of time-domain EMT studies that require adequate representation of harmonics. [ABSTRACT FROM PUBLISHER]

Details

Language :
English
ISSN :
19493029
Volume :
4
Issue :
3
Database :
Complementary Index
Journal :
IEEE Transactions on Sustainable Energy
Publication Type :
Academic Journal
Accession number :
88366608
Full Text :
https://doi.org/10.1109/TSTE.2013.2252209