Back to Search Start Over

Failure of Connecting Clamps in Electrical Terminal Blocks

Authors :
Neidel, A.
Fischer, B.
Giller, M.
Source :
Praktische Metallographie.Practical Metallography; June 2023, Vol. 60 Issue: 6 p382-401, 20p
Publication Year :
2023

Abstract

The failure of fastening elements in electrical terminal blocks was attributed to various material-related causes. While the casehardened terminal screws broke due to hydrogen embrittlement, the material-related cause of the plastic deformations of the roof-shaped washers and the stripping of the threads of the square nuts are undersizing and an insufficient strength for this particular application.

Details

Language :
English
ISSN :
0032678x
Volume :
60
Issue :
6
Database :
Supplemental Index
Journal :
Praktische Metallographie.Practical Metallography
Publication Type :
Periodical
Accession number :
ejs63255249
Full Text :
https://doi.org/10.1515/pm-2023-0031