Abstract
- As cable insulation failure usually started with PD activity, a PD detection system based on pulse current was built to study the PD characteristics of typical defects in XLPE cable. To facilitate the test, the oil cup test terminal was used. Considering the installation procedure, three different kinds of insulation defects in cable accessory samples were made, which were knife incision defect, metal floating potential defect and misplaced stress cone defect. Under long time power frequency voltage of U», 1.7U0, 2.5U0 and 3.5U0 (U0=8.7kV), this paper proposed a variety of methods to characterize partial discharge of these samples by PRPD spectrum, δ t spectrum and PSA spectrum. Results showed the δ t spectrum presented a clear distribution of the peak and the sub-peak. The distribution regularity of partition probability in PSA pattern before the breakdown was found that the probability in the area 1.1 as from 50% to 60%, and the probability in the area 3.1 was from 30% to 40%.
- Subjects :
- Materials science
INSULATION FAILURE
business.industry
Power frequency
020209 energy
Floating potential
Electrical engineering
02 engineering and technology
021001 nanoscience & nanotechnology
Stress (mechanics)
Terminal (electronics)
Partial discharge
0202 electrical engineering, electronic engineering, information engineering
Development (differential geometry)
Composite material
0210 nano-technology
business
Voltage
Subjects
Details
- Database :
- OpenAIRE
- Journal :
- 2017 1st International Conference on Electrical Materials and Power Equipment (ICEMPE)
- Accession number :
- edsair.doi...........0ab1b4b3ef4403813b55e25393de2093