A Transfer Trip Scheme to Supervise Zone 3 Operation
- Source :
- INAE Letters. 1:9-13
- Publication Year :
- 2016
- Publisher :
- Springer Science and Business Media LLC, 2016.
-
Abstract
- Zone 3 of distance relay provides remote backup protection for adjacent transmission lines using local information. At times, zone 3 is prone to maloperation under stressed system conditions, which may cause serious threat to grid security. Zone 3 decisions can be more accurate, if fault pickup information of the adjacent line relays is availed. In this paper, zone 2 pickup signals of adjacent line relays are unified using simple logic gates and the information is transferred to supervise remote backup protection; the zone 3. Proposed method is tested for WSCC nine-bus and two-area four machine systems under different conditions and found to be accurate.
Details
- ISSN :
- 23663278 and 2366326X
- Volume :
- 1
- Database :
- OpenAIRE
- Journal :
- INAE Letters
- Accession number :
- edsair.doi...........1956ed1f9dcc8406e1ddcc0f7f8e2715
- Full Text :
- https://doi.org/10.1007/s41403-016-0002-8