Partial discharge criterion in AC test of oil-immersed transformer and gas-filled transformer in terms of harmful partial discharge level and signal transmission rate

Authors :
S. Okabe
G. Ueta
Source :
IEEE Transactions on Dielectrics and Electrical Insulation. 19:1431-1439
Publication Year :
2012
Publisher :
Institute of Electrical and Electronics Engineers (IEEE), 2012.

Abstract

The soundness of a power transformer under an operating voltage is evaluated in partial discharge (PD) test of long-duration induced ac voltage test. The acceptance criterion for this PD test is 500 pC according to IEC standard; however, few basic data backing this criterion are available. To establish a clear criterion for this PD test, the authors initially conducted a study on the harmful PD level of materials themselves constituting the insulation of an oil-immersed transformer and a gas-filled transformer. This PD level was evaluated based on the rate of decline in the lightning impulse breakdown voltage using the insulating materials themselves and the element models simulating the insulating structure which had been exposed to a PD. Consequently, it emerged that insulations of both types of transformers were degraded if exposed to a PD of 7,000 pC to 10,000 pC. With the safety factor for this PD value taken into account considering the long-term operation and the structural difference of an actual transformer, 5,000 pC was deemed as the harmful PD level at the PD occurrence position. Subsequently, using a winding model of a transformer, PD signal propagation characteristics inside the winding were investigated through actual measurement and analysis. As a result, it was found that the PD having occurred inside the winding is measured as the signal significantly damped depending on the position of occurrence. The transmission rate was 2.2% for an oil-immersed transformer and 2.8% for a gas-filled transformer in the respective lowest cases. What should be controlled in the PD test of an actual transformer is the value of the harmful PD level at the PD occurrence position multiplied by the transmission rate at the PD detection position. Therefore, the conclusion was reached that the acceptance criterion in the test should be set to 5,000 pC × 2.2% = 110 pC or less for an oil-immersed transformer and 5,000 pC × 2.8% = 140 pC or less for a gas-filled transformer, respectively.

Details

ISSN :
10709878
Volume :
19
Database :
OpenAIRE
Journal :
IEEE Transactions on Dielectrics and Electrical Insulation
Accession number :
edsair.doi...........3d141d01e00826f18e68dfa19ab3163e