Back to Search Start Over

Surge voltages and currents into a customer due to nearby lightning

Authors :
Yoshiyuki Nagai
Akihiro Ametani
Kae Matsuoka
Hiroshi Omura
Source :
Electric Power Systems Research. 79:428-435
Publication Year :
2009
Publisher :
Elsevier BV, 2009.

Abstract

This paper presents experimental results of lightning surges incoming into a customer due to lightning to an antenna of the customer, a pole and a ground nearby the customer, and briefly discusses lightning current distribution in the customer, a distribution line and a telephone line. Based on experimental results, modeling of each component is explained, and EMTP simulations are carried out. The ground voltage rise is represented by a mutual resistance between grounding electrodes. EMTP simulation results have been observed to agree qualitatively with the measured results, and it becomes possible to investigate lightning surges and current distribution in a customer by an EMTP simulation.

Details

ISSN :
03787796
Volume :
79
Database :
OpenAIRE
Journal :
Electric Power Systems Research
Accession number :
edsair.doi...........77b8381727aa1f4c57aba03f3c6b763d
Full Text :