Back to Search
Start Over
Surge voltages and currents into a customer due to nearby lightning
- Source :
- Electric Power Systems Research. 79:428-435
- Publication Year :
- 2009
- Publisher :
- Elsevier BV, 2009.
-
Abstract
- This paper presents experimental results of lightning surges incoming into a customer due to lightning to an antenna of the customer, a pole and a ground nearby the customer, and briefly discusses lightning current distribution in the customer, a distribution line and a telephone line. Based on experimental results, modeling of each component is explained, and EMTP simulations are carried out. The ground voltage rise is represented by a mutual resistance between grounding electrodes. EMTP simulation results have been observed to agree qualitatively with the measured results, and it becomes possible to investigate lightning surges and current distribution in a customer by an EMTP simulation.
Details
- ISSN :
- 03787796
- Volume :
- 79
- Database :
- OpenAIRE
- Journal :
- Electric Power Systems Research
- Accession number :
- edsair.doi...........77b8381727aa1f4c57aba03f3c6b763d
- Full Text :
- https://doi.org/10.1016/j.epsr.2008.09.005