Back to Search Start Over

The Positive Role of the Partial Discharge Monitoring System in the Partial Discharge Detection of GIS Equipment

Authors :
Jiangtian Chen
Dongliang Wei
Zhi Wang
Congcong Liu
Weitao Shao
Weiling Shao
Source :
Journal of Physics: Conference Series. 2224:012046
Publication Year :
2022
Publisher :
IOP Publishing, 2022.

Abstract

When gas insulated metal enclosed switchgear and controlgear (GIS) has internal discharge, some faults are difficult to find during inspections due to the enclosed metal casing. This paper introduces the event of the floating potential discharge inside the GIS equipment of a 500kV substation found by GIS on-line monitoring system. Through on-site ultra-high frequency detection and precise positioning of the oscilloscope to determine the position of the discharge source at a certain switch, combined with the disassembly of the equipment, it is determined that the equipment defect is the discharge of the floating electrode of the switch fork.The results show that the on-line monitoring of GIS partial discharge has an important reference role in discovering the internal discharge of equipment during the test interval, and the monitoring and maintenance of GIS partial discharge on-line monitoring system should be strengthened in daily work.

Details

ISSN :
17426596 and 17426588
Volume :
2224
Database :
OpenAIRE
Journal :
Journal of Physics: Conference Series
Accession number :
edsair.doi...........8ac496914c95d1f9c93474b6c183bff4
Full Text :
https://doi.org/10.1088/1742-6596/2224/1/012046