Back to Search
Start Over
Fault Waveform Analysis from Different CTs for Fault Location
- Source :
- 2018 International Conference on Power System Technology (POWERCON).
- Publication Year :
- 2018
- Publisher :
- IEEE, 2018.
-
Abstract
- This paper investigates a typical 220kV GIS circuit breaker re-ignition fault in practical systems. All types of protection, such as transmission line protection, circuit break failure protection, bus-bar protection and transform protection, coordinate in one fault case. The protection behavior is analyzed. By reproducing the fault process, the coordination among line protections, circuit break failure protections, bus bar protections and transformer neutral point gap protections are studied. The evidence for protection configurations and settings is provided. According to the comparisons between the fault data from the fault recorder and from the busbar protection device, the bus bar differential current is calculated. Analysis result from different current transformers (CTs) verified the fault locations.
- Subjects :
- Ground
Busbar
business.industry
Computer science
020209 energy
Electric breakdown
Electrical engineering
ComputingMilieux_LEGALASPECTSOFCOMPUTING
02 engineering and technology
Current transformer
law.invention
Transmission line protection
Waveform analysis
law
0202 electrical engineering, electronic engineering, information engineering
Transformer
business
Circuit breaker
Subjects
Details
- Database :
- OpenAIRE
- Journal :
- 2018 International Conference on Power System Technology (POWERCON)
- Accession number :
- edsair.doi...........a9260ebf19bb2bd6c2b405bd8e557021