Back to Search Start Over

Mapping of optimum operating condition for LiBr–water refrigeration cycles

Authors :
Nilesh A. Mali
Sunil S. Bhagwat
Source :
Sādhanā. 42:257-269
Publication Year :
2017
Publisher :
Springer Science and Business Media LLC, 2017.

Abstract

In this work, optimum operating condition maps are generated covering wide ranges of refrigeration and sink temperatures for single- and double-effect LiBr–water vapour absorption refrigeration cycle. These optimum condition maps will be useful to choose optimum operating conditions while designing LiBr–water cycle for desired applications. Methodology for generating such maps is discussed in detail, which can also be used for other absorption refrigeration cycles with various working fluids. Three configurations of LiBr–water absorption refrigeration cycles, single effect, double-effect series flow and double-effect parallel flow, are analysed with the most accurate thermodynamic property correlation available in the literature. Sensitivity of cycle performance to various operating variables such as generator, absorber and condenser temperatures is determined. Second law analysis shows that when a higher temperature heat source is available, double-effect cycles are more effective over single effect as they have higher coefficient of performance.

Details

ISSN :
09737677 and 02562499
Volume :
42
Database :
OpenAIRE
Journal :
Sādhanā
Accession number :
edsair.doi...........b2a1320a137ce952340e302d8a03f2e0
Full Text :
https://doi.org/10.1007/s12046-017-0597-9