Back to Search
Start Over
Mapping of optimum operating condition for LiBr–water refrigeration cycles
- Source :
- Sādhanā. 42:257-269
- Publication Year :
- 2017
- Publisher :
- Springer Science and Business Media LLC, 2017.
-
Abstract
- In this work, optimum operating condition maps are generated covering wide ranges of refrigeration and sink temperatures for single- and double-effect LiBr–water vapour absorption refrigeration cycle. These optimum condition maps will be useful to choose optimum operating conditions while designing LiBr–water cycle for desired applications. Methodology for generating such maps is discussed in detail, which can also be used for other absorption refrigeration cycles with various working fluids. Three configurations of LiBr–water absorption refrigeration cycles, single effect, double-effect series flow and double-effect parallel flow, are analysed with the most accurate thermodynamic property correlation available in the literature. Sensitivity of cycle performance to various operating variables such as generator, absorber and condenser temperatures is determined. Second law analysis shows that when a higher temperature heat source is available, double-effect cycles are more effective over single effect as they have higher coefficient of performance.
- Subjects :
- Engineering
Multidisciplinary
Parallel flow
business.industry
020209 energy
Nuclear engineering
Heat pump and refrigeration cycle
010102 general mathematics
Second law analysis
Refrigeration
Thermodynamics
02 engineering and technology
Operating variables
Coefficient of performance
01 natural sciences
law.invention
Single effect
law
0202 electrical engineering, electronic engineering, information engineering
Absorption refrigerator
0101 mathematics
business
Subjects
Details
- ISSN :
- 09737677 and 02562499
- Volume :
- 42
- Database :
- OpenAIRE
- Journal :
- Sādhanā
- Accession number :
- edsair.doi...........b2a1320a137ce952340e302d8a03f2e0
- Full Text :
- https://doi.org/10.1007/s12046-017-0597-9