Back to Search Start Over

Modeling of Current-Limiting Circuit Breakers for the Calculation of Short-Circuit Current

Authors :
Huaren Wu
Lin Sun
Ling Yuan
Xiaohui Li
Source :
IEEE Transactions on Power Delivery. 30:652-656
Publication Year :
2015
Publisher :
Institute of Electrical and Electronics Engineers (IEEE), 2015.

Abstract

A current-limiting circuit breaker (CLCB) can quickly interrupt circuit faults and limit the short-circuit current. Modeling of a CLCB is important for the calculation of short-circuit current and arc flash energy. Based on the analysis of the arc voltage waveforms of CLCBs, a new arc model is derived. The Schwarz arc model and arc length are used to represent the complicated voltages of CLCBs, and arc length is determined from a differential equation. The test results of a commercial CLCB sequentially deployed in a couple of three-phase power systems are studied, and the parameters of the model are obtained. The three-phase faults in the power systems are simulated. The short-circuit currents and voltages of the CLCB are calculated and compared to the test results. The simulation results are in good agreement with the test data, and the proposed model can predict the high-current arcs in CLCBs. These techniques facilitate the calculation of short-circuit currents.

Details

ISSN :
19374208 and 08858977
Volume :
30
Database :
OpenAIRE
Journal :
IEEE Transactions on Power Delivery
Accession number :
edsair.doi...........bb406b3936203b56e839a4e21546799a
Full Text :
https://doi.org/10.1109/tpwrd.2014.2305166