Back to Search Start Over

Improvement of Withstand Voltage at Particle Contamination in DC-GIS Due to Dielectric Coating on Conductor

Authors :
Masayuki Hatano
Haruhisa Fujii
A. Kawahara
Koichiro Nakanishi
T. Hasegawa
Hiroyuki Hama
Kiyoshi Inami
Manabu Yoshimura
Source :
Gaseous Dielectrics VIII ISBN: 9781461372219
Publication Year :
1998
Publisher :
Springer US, 1998.

Abstract

±500kV DC transmission between Honshu island and Shikoku island in Japan will be operated at the beginning of the next century. High voltage DC-Gas Insulated Switchgear (DC-GIS) equipped in the DC-AC converter station has been developed. One of considerable items for designing the DC-GIS is the effect of the particle contamination to electrical properties more crucial than conventional GIS. the particles floating around the high voltage conductor with negative DC voltage give the most detrimental effect to the insulation properties at application of positive lightning impulse. Therefore it is essential to study and elucidate the phenomena for the realization of compact and highly reliable DC-GIS.

Details

ISBN :
978-1-4613-7221-9
ISBNs :
9781461372219
Database :
OpenAIRE
Journal :
Gaseous Dielectrics VIII ISBN: 9781461372219
Accession number :
edsair.doi...........ced90943e0508466f29c55a3caf3c676
Full Text :
https://doi.org/10.1007/978-1-4615-4899-7_76