A Single-Ended Fault Location Method for Grid-Connected Converter System Based on Control and Protection Coordination
- Source :
- IEEE Transactions on Power Delivery. 37:3071-3081
- Publication Year :
- 2022
- Publisher :
- Institute of Electrical and Electronics Engineers (IEEE), 2022.
-
Abstract
- Traditional single-ended fault location method is influenced by the fault resistance and the remote in feed, which reflects as the two equations built by fault phase have four unknowns. And in the grid-connected converter system, the weak feedback characteristic further reduces the performance of the method. To solve it, a single-ended fault location method based on control and protection coordination is proposed in this paper. First, using the high controlled-ability of the converter, the control strategy for fault ride-through (FRT) operation is divided into two stages by switching control modes. Then, according to the electrical quantities under two stages, four uncorrelated equations can be established, and the equations still have four unknown parameters. The fault distance can be calculated by solving them. The simulation results show that the proposed method has high accuracy and is immune to fault resistance and fault location, it solves the problem of insufficient equations in principle.