Back to Search Start Over

Energy Consumption and Feasibility Study of a Hybrid Desiccant Dehumidification Air Conditioning System in Beirut

Authors :
M. Othmani
Kamel Ghali
Nesreen Ghaddar
Source :
International Journal of Green Energy. 5:360-372
Publication Year :
2008
Publisher :
Informa UK Limited, 2008.

Abstract

This work studies the economic feasibility of integrating a rotary solid desiccant wheel with the conventional vapor compression air-conditioning system in the city of Beirut. To increase the economic practicality of such a hybrid system, the combined system utilizes the heat dissipated by the condenser and natural gas heat energy in regenerating the desiccant wheel. A heat and mass transfer desiccant model is developed to study the hourly performance of the hybrid system when used in air conditioning a typical auditorium (150 m2) over the entire cooling season. The economic performance of the hybrid system is compared with the conventional air-conditioning system while varying the number of occupants in the auditorium from 10 to 100 to change the sensible heat ratio from 0.53 to 0.27 and the percentage of the outside fresh air from 25% to 100%. The conventional system cooling load range was between 9.2 kW and 63.4 kW for the cases simulated in this work, while the vapor compression subsystem varied in th...

Details

ISSN :
15435083 and 15435075
Volume :
5
Database :
OpenAIRE
Journal :
International Journal of Green Energy
Accession number :
edsair.doi...........ef726f8e5a784e6ac4942db43fa86b92
Full Text :
https://doi.org/10.1080/15435070802414280