Back to Search Start Over

Impulse puncture characteristics of mass-impregnated paper-insulated cables, with special reference to testing procedures

Authors :
P.R. Howard
Source :
Proceedings of the IEE - Part II: Power Engineering. 100:315-318
Publication Year :
1953
Publisher :
Institution of Engineering and Technology (IET), 1953.

Abstract

The influence of polarity, polarity reversal, repeated stressing, waveshape and conductor size on the impulse puncture voltage for three sizes of single-conductor mass-impregnated 33-kV cable has been investigated. Experimental results are discussed and conclusions drawn from which a test for incorporation in a cable specification and the revision of B.S. 923: 1940 for cables has been suggested.