Back to Search Start Over

FOP - FSM Measurement – Relative Position of the Test Conductors

Authors :
Kostić, Vojin
Raičević, Nebojša
Dočić, Miroslav
Source :
2020 21st International Symposium on Electrical Apparatus & Technologies (SIELA).
Publication Year :
2020
Publisher :
IEEE, 2020.

Abstract

Experimental evaluation of the measurement results based on FSM (Frequency Shift Method) concept in the non-conventional FOP (Fall-of-Potential) measuring scheme, for different angles between the test conductors, is presented in this paper. As it is well known, the optimal angle between the test conductors is θ = 90°. However, in practice, most often because of the physical obstacles in the surround substation, this condition cannot be provided. We have experimentally determined that the angle between the test conductors must be less than 60° relative to the optimal angle θ. In that case the corresponding measurement error is less than 3%.

Details

Database :
OpenAIRE
Journal :
2020 21st International Symposium on Electrical Apparatus & Technologies (SIELA)
Accession number :
edsair.doi.dedup.....31f195f5090987a1dce5570b1f3a6cb6
Full Text :
https://doi.org/10.1109/siela49118.2020.9167037