Currents Distribution During a Fault in an MV Network: Methods and Measurements

Authors :
Giuseppe Parise
Roberto Napoli
Gaetano Zizzo
Francesco Torelli
Luigi Parise
Giovanni Valtorta
Angelo De Simone
Riccardo Tommasini
G. Cafaro
Pasquale Montegiglio
Eleonora Riva Sanseverino
Pietro Colella
Maria Luisa Di Silvestre
E. Morozova
F. Tummolillo
A. Barresi
Luigi Martirano
Enrico Pons
Colella, P.
Napoli, R.
Pons, E.
Tommasini, R.
Barresi, A.
Cafaro, G.
De Simone, A.
Di Silvestre, M.
Martirano, L.
Montegiglio, P.
Morozova, E.
Parise, G.
Parise, L.
Riva Sanseverino, E.
Torelli, F.
Tummolillo, F.
Valtorta, G.
Zizzo, G.
Publication Year :
2016
Publisher :
ieee, 2016.

Abstract

When a single line to ground fault happens on the MV side of a HV/MV system, only a small portion of the fault current is injected into the ground by the ground-grid of the faulty substation. In fact the fault current is distributed between grounding electrodes and MV cables sheaths. In systems with isolated neutral or with resonant earthing this may be sufficient to provide safety from electric shock. Experimental measurements were performed on a real MV distribution network: a real single line to ground fault was made and fault currents were measured in the faulty substation and in four neighboring substations. In this paper the problem of fault current distribution is introduced, the test system is described and the measurements results are presented.