Analysis on impacts of the shunt conductances in multi-terminal HVDC grids optimal power-flow

Authors :
Kumars Rouzbehi
Pedro Rodriguez
Jafar Milimonfared
J. Ignacio Candela
Seyed Saeid Heidary Yazdi
Universitat Politècnica de Catalunya. Departament d'Enginyeria Elèctrica
Universitat Politècnica de Catalunya. SEER - Sistemes Elèctrics d'Energia Renovable
Source :
IECON, UPCommons. Portal del coneixement obert de la UPC, Universitat Politècnica de Catalunya (UPC), Recercat. Dipósit de la Recerca de Catalunya, instname
Publication Year :
2017
Publisher :
IEEE, 2017.

Abstract

This study deals with impacts of the shunt conductances associated with HVDC cables and VSC-HVDC stations on optimal operation of Multi-Terminal HVDC (MT-HVDC). In this study, for the first time, shunt conductances are integrated to HVDC Optimal Power-Flow (OPF) program that is executed at the Power Dispatch Center (PDC) of the MT-HVDC grid. With the objective of losses minimization, optimal reference operation points of the VSC-HVDC stations are derived. The operating points of the power converter stations are adjusted based on the calculations performed in the dispatch center. CIGRE DCS3 MT-HVDC grid, structured by CIGRE B4 working group, is taken as the test platform. Test results have revealed the optimum voltages and loss pattern change. Moreover, the findings are compared with the case of neglecting the shunt conductances.