Investigating the effect of interstage pressure on cooling performance of a real-world CO2 heat pump system

Authors :
Ji Wang
Martin Belusko
Hesam Semsarilar
Michael Evans
Ming Liu
Frank Bruno
EEEP2021: The Sixth International Conference on Energy Engineering and Environmental Protection 16-18 November 2021 Virtual event
Wang, Ji
Belusko, Martin
Semsarilar, Hesam
Evans, Michael
Liu, Ming
Bruno, Frank
Publication Year :
2022
Publisher :
IOP Publishing : UK, 2022.

Abstract

The study reveals the effect of interstage pressure with the consideration of gas cooler outlet temperature on the cooling performance of an operating CO2 heat pump system currently in use at a dairy plant. Based on the numerical model and CO2 properties, it was found that the maximum mass fraction of liquid allocated for cooling can be achieved in the middle of the operating range of interstage pressure when the enthalpy at the location of the gas cooler outlet is between 341 kJ/kg. K and 399 kJ/kg. K (that is, the gas cooler outlet temperature is between 37.34 °C and 43.02 °C with a fixed discharge pressure of 85 bar), however, the maximum liquid fraction can be achieved at the upper limit of the pressure when the enthalpy is less than 341 kJ/kg. K and can be achieved at the lower limit of the pressure when the enthalpy is higher than 399 kJ/kg. K, respectively. In the comparative study on fixed and variable interstage pressure, it was found that there is small difference in cooling COP when the gas cooler outlet temperature is lower than 38.5 °C , while the COPs with variable interstage pressures surpass those with fixed pressures when the gas cooler outlet temperatures are even higher.

Details

Language :
English
Database :
OpenAIRE
Accession number :
edsair.doi.dedup.....ce91b0e4c8bd417ca66b15cf72bae8c8