Full scale tests of the base-isolation system for an emergency hospital
- Publication Year :
- 2019
- Publisher :
- Institute of Structural Analysis and Antiseismic Research School of Civil Engineering National Technical University of Athens (NTUA), 2019.
-
Abstract
- The paper presents the results of some full-scale tests regarding the base-isolation system of the emergency room building of the polyclinic hospital in Palermo (Italy). This building has been recently realized and its base isolation system is characterized by double friction pendulum isolators. Static lateral pushing tests were aimed at identifying fundamental mechanical properties of the whole isolation level (e.g. friction forces and stiffness) in order to verify the agreement with the design hypotheses. Further dynamic tests provided different displacements of the isolated base followed by the instantaneous release (snap-back tests), in order to verify the effectiveness, the mechanical parameter in dynamics and re-centering capacity of the isolation system. The design of both the types of test and the respective results and interpretations are illustrated in the paper highlighting a number of issues arising when arranging such kind of investigations on full scale buildings.
- Subjects :
- Settore ICAR/09 - Tecnica Delle Costruzioni
full-scale experimental tests
Computer science
seismic isolation
snap-back test
Seismic isolation
friction
Friction pendulum bearing, seismic isolation, snap-back test, friction, in-situ testing, full-scale experimental tests
Full scale test
Base isolation
Friction pendulum bearing
in-situ testing
Marine engineering
Subjects
Details
- Language :
- English
- Database :
- OpenAIRE
- Accession number :
- edsair.doi.dedup.....dfcbec2351a38b38498c94ce92dd8254