Metrological Qualification of PD Analysers for Insulation Diagnosis of HVDC and HVAC Grids

Authors :
Fernando Garnacho
Fernando Álvarez
Alf-Peter Elg
Christian Mier
Kari Lahti
Abderrahim Khamlichi
Eduardo Arcones
Joni Klüss
Armando Rodrigo Mor
Pertti Pakonen
José Ramón Vidal
Álvaro Camuñas
Jorge Rovira
Carlos Vera
Miran Haider
Source :
Sensors, Vol 23, Iss 14, p 6317 (2023)
Publication Year :
2023
Publisher :
MDPI AG, 2023.

Abstract

On-site partial discharge (PD) measurements have turned out to be a very efficient technique for determining the insulation condition in high-voltage electrical grids (AIS, cable systems, GIS, HVDC converters, etc.); however, there is not any standardised procedure for determining the performances of PD measuring systems. In on-line and on-site PD measurements, high-frequency current transformers (HFCTs) are commonly used as sensors as they allow for monitoring over long distances in high-voltage installations. To ensure the required performances, a metrological qualification of the PD analysers by applying an evaluation procedure is necessary. A novel evaluation procedure was established to specify the quantities to be measured (electrical charge and PD repetition rate) and to describe the evaluation tests considering the measured influence parameters: noise, charge amplitude, pulse width and time interval between consecutive pulses. This procedure was applied to different types of PD analysers used for off-line measurements, sporadic on-line measurements and continuous PD monitoring. The procedure was validated in a round-robin test involving two metrological institutes (RISE from Sweden and FFII from Spain) and three universities (TUDelft from the Netherlands, TAU from Finland and UPM from Spain). With this round-robin test, the effectiveness of the proposed qualification procedure for discriminating between efficient and inappropriate PD analysers was demonstrated. Furthermore, it was shown that the PD charge quantity can be properly determined for on-line measurements and continuous monitoring by integrating the pulse signals acquired with HFCT sensors. In this case, these sensors must have a flat frequency spectrum in the range between several tens of kHz and at least two tens of MHz, where the frequency pulse content is more significant. The proposed qualification procedure can be useful for improving the future versions of the technical specification TS IEC 62478 and the standard IEC 60270.

Details

Language :
English
ISSN :
14248220
Volume :
23
Issue :
14
Database :
Directory of Open Access Journals
Journal :
Sensors
Publication Type :
Academic Journal
Accession number :
edsdoj.0141dcf4dab8410aa9cd667bad49a169
Document Type :
article
Full Text :
https://doi.org/10.3390/s23146317