Induced Overvoltage Caused by Indirect Lightning Strikes in Large Photovoltaic Power Plants and Effective Attenuation Techniques

Authors :
Ahmed I. Omar
Moustafa Mohsen
Mousa A. Abd-Allah
Zakaria M. Salem Elbarbary
Abdelrahman Said
Source :
IEEE Access, Vol 10, Pp 112934-112947 (2022)
Publication Year :
2022
Publisher :
IEEE, 2022.

Abstract

Indirect Lightning Stroke (ILS) is considered an urgent issue on overall power systems due to its sudden dangerous occurrence. A grid-connected solar Photovoltaic (PV) power plant of 1MW was considered and analyzed using PSCAD/EMTDC software. The effect of grounding grid resistance ( $R_{g}$ ) on the induced voltages caused by the indirect strokes was discussed. The Transient Grounding Potential Rise (TGPR) variation with $R_{g}$ was presented and discussed. Four different models were proposed and installed for the system under study, which includes a combination of the Externally Gapped Line Arrester (EGLA) with the Non-Gapped Line Arrester (NGLA). The results show that when the $R_{g}$ was reduced from 5 to 1 ohm, TGPR decreased by about 79.63%, whereas the peak value was reduced by about 91.3% nearby the striking position. Four models of EGLAs were proposed to reduce the induced transient overvoltage effectively. The four models showed a remarkable ability to reduce the backflow current (BFC) and, consequently, the induced overvoltage. The EGLA’s type with the composite air gap reduced the TGPR by about 77.04 % and reduced the induced overvoltage nearby the striking position by about 51.3%.

Details

Language :
English
ISSN :
21693536
Volume :
10
Database :
Directory of Open Access Journals
Journal :
IEEE Access
Publication Type :
Academic Journal
Accession number :
edsdoj.05c0f2b01cf6434a9b10d347f56912ea
Document Type :
article
Full Text :
https://doi.org/10.1109/ACCESS.2022.3216866