Back to Search Start Over

Load angle estimation of synchronous generator

Authors :
Veinović Slavko
Janda Žarko
Stojić Đorđe
Dragosavac Jasna
Joksimović Dušan
Klasnić Ilija
Đorđević Milan
Source :
Zbornik Radova: Elektrotehnički Institut "Nikola Tesla", Vol 30, Iss 30, Pp 81-91 (2020)
Publication Year :
2020
Publisher :
Electrical Engineering Institute Nikola Tesla, 2020.

Abstract

In this paper a load angle estimation method of round rotor synchronous generator is presented, for load angle limiter in AVR systems design purpose. To get information of load angle, it is necessary to have values of the one terminal voltage, one phase current and q-axis reactance Xq. Mentioned values are acquired by synchronous sampling technique and processed by discrete Fourier transformation. The accuracy of presented method highly depends on quality of zero-crossing detection of the input voltage signal and on the calculation estimation of the fundamental frequency. This method is of reduced sensitivity to higher harmonics presence contence in voltages and current waveforms. Another advantage, when compared to other dq or ab based calculations estimations, is the necessity of use only two measurement channels. Drawback of described approach is lack of immunity to current asymmetry. However, a solution to overcome this problem is offered by introducing the additional measurements into the algorithm to extract the synchronous sampled direct components of all three phase currents.

Details

Language :
English, Serbian
ISSN :
03508528 and 24061212
Volume :
30
Issue :
30
Database :
Directory of Open Access Journals
Journal :
Zbornik Radova: Elektrotehnički Institut "Nikola Tesla"
Publication Type :
Academic Journal
Accession number :
edsdoj.0b6b4f7302e9446aa6dd8896ea423f35
Document Type :
article