Back to Search Start Over

User-Defined Dual Setting Directional Overcurrent Relays with Hybrid Time Current-Voltage Characteristics-Based Protection Coordination for Active Distribution Network

Authors :
Lucheng Hong
Mian Rizwan
Muhammad Wasif
Shafiq Ahmad
Mazen Zaindin
Muhammad Firdausi
Source :
IEEE Access, Vol 9, Pp 62752-62769 (2021)
Publication Year :
2021
Publisher :
IEEE, 2021.

Abstract

With the penetration of renewable energy sources based distributed generation (RES-DG) in the distribution network (DN), the operating time of protection relays becomes a major concern to avoid the mis-coordination and nuisance tripping of RES-DG. It is due to the bidirectional flow of current, variance in the fault current level, i.e. high fault current in case of Squirrel cage induction generator (SCIG) based RES-DG, and low fault current for an inverter-based RES-DGs. This paper proposes a novel User-defined dual setting direction overcurrent relay with hybrid time current-voltage (UDDOR-TCV) characteristics to intensify the proposed scheme’s flexibility without any communication assistance for radial DN. The proposed model is formulated in a constrained non-linear optimization fashion and solved with the MINLP solver of general algebraic modelling system(GAMS) software to determine the optimal relay settings. The propounded protection scheme is simulated on IEEE-33 bus radial distribution system and a local 40-bus system hosting the multiple SCIG and PV based RES-DGs at optimal locations. Detailed numerical studies are carried out to show the performance of the proposed scheme. 66.848% and 68.26% reduction in relay operation time with zero mis-coordination is achieved with SCIG-WTG case and PV-units case for the IEEE-33 bus system and a similar reduction in operation time is 68.937% and 66.563% for Local-40 bus system. Moreover, the relays numbers are reduced by 32.692% and 39.7% for IEEE-33 and Local-40 bus systems, respectively, due to the forward/reverse characteristics capability of the proposed UDDOR-TCV. The performance of the proposed scheme is also evaluated on IEEE-8 bus meshed DN. The results are compared with the existing protection schemes in recent literature.

Details

Language :
English
ISSN :
21693536
Volume :
9
Database :
Directory of Open Access Journals
Journal :
IEEE Access
Publication Type :
Academic Journal
Accession number :
edsdoj.56da911a8d544ba383a837ecfac831da
Document Type :
article
Full Text :
https://doi.org/10.1109/ACCESS.2021.3074426