Abstract
- The tracking of a given voltage in the traditional double closed-loop proportional integral control in the current power grid simulator has problems such as static difference, delay and oscillation. It is proposed that the voltage outer loop and current inner loop of the inverter side of the power grid simulator adopt proportional integral and quasi-proportional resonance control respectively, and the topology of the inverter adopts a cascaded modular design to establish a single-phase inverter model. Compared with the traditional double closed-loop proportional-integral control, it is verified that the proportional-integral-quasi-proportional resonant controller can effectively improve the system’s ability to track the command voltage and the stability of the output voltage.