Back to Search Start Over

Partial discharge pattern recognition method for mine-used dry-type transformer

Authors :
TANG Jianwei
SU Hong
YAN Jiaming
ZHANG Jianwen
WANG Jinchuan
WANG Enjun
Source :
Gong-kuang zidonghua, Vol 45, Iss 1, Pp 76-80 (2019)
Publication Year :
2019
Publisher :
Editorial Department of Industry and Mine Automation, 2019.

Abstract

In order to improve recognition accuracy of partial discharge pattern of mine-used dry-type transformer, a partial discharge pattern recognition method for mine-used dry-type transformer was proposed. Firstly, orthogonal matching pursuit algorithm is used to denoise original partial discharge signal, which can retain useful information of the original partial discharge signal to the greatest extent. Then, autoregressive coefficient features of the partial discharge signal after denoising are extracted by autoregressive model. Finally, the autoregressive coefficient features are input into random forest integrated classifier to recognize partial discharge pattern. The experimental result shows that average recognition accuracy of the method is 98%.

Details

Language :
Chinese
ISSN :
1671251X and 1671251x
Volume :
45
Issue :
1
Database :
Directory of Open Access Journals
Journal :
Gong-kuang zidonghua
Publication Type :
Academic Journal
Accession number :
edsdoj.88903b3a14ad9b921f995af157f11
Document Type :
article
Full Text :
https://doi.org/10.13272/j.issn.1671-251x.2018090081