Back to Search
Start Over
THE DEGREE OF POLYMERIZATION OF POWER TRANSFORMERS’ PAPER INSULATION
- Source :
- Известия высших учебных заведений: Проблемы энергетики, Vol 20, Iss 9-10, Pp 34-38 (2019)
- Publication Year :
- 2019
- Publisher :
- Kazan State Power Engineering University, 2019.
-
Abstract
- The paper presents the results of research and analysis of literature data on the paper insulation's thermal aging. An exponential decrease in the degree of polymerization of paper insulation from the aging time is established, at the starting time of transformers’ operation the aging rate of paper insulation is maximal and after that its slowing down. It was found out that the degree of polymerization at the starting time of the transformer's operation can be in the range of 900 units, this is due to its drying during the manufacturing process.
Details
- Language :
- English, Russian
- ISSN :
- 19989903
- Volume :
- 20
- Issue :
- 9-10
- Database :
- Directory of Open Access Journals
- Journal :
- Известия высших учебных заведений: Проблемы энергетики
- Publication Type :
- Academic Journal
- Accession number :
- edsdoj.908c1d5511424377b02ca40889367f9f
- Document Type :
- article
- Full Text :
- https://doi.org/10.30724/1998-9903-2018-20-9-10-34-38