Dynamic thermal rating assessment of oil‐immersed power transformers for multiple operating conditions

Authors :
Chen Zhang
Xuzhu Dong
Jiangjun Ruan
Yongqing Deng
Source :
High Voltage, Vol 9, Iss 1, Pp 195-205 (2024)
Publication Year :
2024
Publisher :
Wiley, 2024.

Abstract

Abstract In this article, the dynamic thermal rating assessment method of oil‐immersed power transformer with multiple operating conditions is proposed, considering the constraints of hot spot temperature (HST), top oil temperature, losses of life and the maximum allowable current of on‐load tap changer (OLTC) or bushing, which can determine the dynamic load curves under different operating conditions and give the most sensitive constraints to limit the dynamic load capacity. To improve the accuracy of HST estimation, the temperature estimation model is also improved and the thermal parameters are optimised using the HST measured by optical fibre. Finally, several application examples are studied for transformers in different scenarios. The results show that the normal cyclic dynamic transformer rating (DTR) is mainly limited by the losses of life when the ambient temperature is high, and the average load factor can be increased to 0.82 with a maximum load capacity of 1.23. The main limiting factor of short‐term DTR is the OLTC or bushing current constraint, and the average load factor can be increased to 1.00. The maximum load capacity of the transformer under both operating conditions is 23% and 50% higher than its rated load capacity, indicating that the transformer still has a large load potential available.

Details

Language :
English
ISSN :
23977264 and 12730149
Volume :
9
Issue :
1
Database :
Directory of Open Access Journals
Journal :
High Voltage
Publication Type :
Academic Journal
Accession number :
edsdoj.f079df12730149a2a13106dd36214abd
Document Type :
article
Full Text :
https://doi.org/10.1049/hve2.12333