Study on Shock Disinfection in a Fire Extinguishing Water Supply System

Authors :
Kun Xiang
Pan Geng
Xuan Sun
Shasha Yuan
Peng Du
Xing Li
Source :
Water, Vol 13, Iss 21, p 2967 (2021)
Publication Year :
2021
Publisher :
MDPI AG, 2021.

Abstract

The biofilms generated in a fire extinguishing water supply system can cause corrosion and a reduction in the water supply capacity; thus, degrading the system performance. To mitigate microbial corrosion, appropriate disinfection measures are necessary. In this study, the secondary addition of chlorine is employed to investigate the kinetics of chlorine decay, and shock disinfection is applied to investigate the removal efficiency of corrosion bacteria, and the microbial composition of a biofilm on the pipe wall was also clarified. The results show that the residual chlorine content in the secondary chlorination process was directly correlated with the decay rate of residual chlorine and the corrosion rate of the pipe wall. Additionally, the chlorine impact disinfection method could reduce the electrochemical corrosion phenomenon of the pipe wall. When the concentration of chlorine was 3 mg/L, the removal rate of corrosion bacteria was higher in 60 min than in 30 min. Specifically, most of the bacteria were inactivated in 60 min and the biofilm was severely damaged. Shock disinfection could significantly inactivate all microflora in the biofilm; the relative abundances of microflora varied significantly, while the change of microflora at the phylum level was insignificant. This study can provide theoretical support for the secondary addition of chlorine and shock disinfection in a fire extinguishing water supply system.

Details

Language :
English
ISSN :
20734441
Volume :
13
Issue :
21
Database :
Directory of Open Access Journals
Journal :
Water
Publication Type :
Academic Journal
Accession number :
edsdoj.f80a0d7404094f5ea364f7ad723c51f1
Document Type :
article
Full Text :
https://doi.org/10.3390/w13212967