Back to Search Start Over

Improved transient simulation of salient-pole synchronous generators with internal and ground faults in the stator winding

Authors :
Bi, Daqiang
Wang, Xiangheng
Wang, Weijian
Zhu, Z.Q.
Howe, David
Source :
IEEE Transactions on Energy Conversion. March, 2005, Vol. 20 Issue 1, p128, 7 p.
Publication Year :
2005

Abstract

An improved model for simulating the transient behavior of salient-pole synchronous generators with internal and ground faults in the stator winding is established using the multiloop circuit method. The model caters for faults under different ground conditions for the neutral, and accounts for the distributed capacitances of the windings to ground. Predictions from the model are validated by experiments, and it is shown that the model accurately predicts the voltage and current waveforms under fault conditions. Hence, it can be used to analyze important features of faults and to design appropriate protection schemes. Index Terms--Ground fault, internal fault, multiloop circuit method, salient-pole generator.