Characterization of Distribution Power Quality Events with Fourier and Wavelet Transforms
- Source :
- IEEE Transactions on Power Delivery. Jan, 2000, Vol. 15 Issue 1, 247
- Publication Year :
- 2000
-
Abstract
- It is the objective of this paper to present unique features that characterize power quality events and methodologies to extract them from recorded voltage and/or current waveforms using Fourier and wavelet transforms. Examples of unique features include peak amplitudes, RMS, frequency, and statistics of wavelet transform coefficients. These features are derived from well documented theories, power engineers' heuristics gained through long years of experience, and power quality data collected in recent years. Converter operation, transformer energization, and capacitor energization (which includes normal, back-to-back, and restrike on opening energization), representing three common power quality events at the distribution level, are presented. These examples provide the basis for further characterization of other power quality events. Index Terms--Fourier and wavelet transforms, identifying features, power quality.