Numerical electromagnetic field analysis of archorn voltages during a back-flashover on a 500-kV twin-circuit line
- Source :
- IEEE Transactions on Power Delivery. Jan, 2003, Vol. 18 Issue 1, p207, 6 p.
- Publication Year :
- 2003
-
Abstract
- Archorn voltages of a simulated 500-kV twin-circuit line, in the case of one-phase back-flashover due to lightning to a tower top, are analyzed by the thin-wire time-domain analysis (TWTDA) code. Prior to this analysis, a recently proposed flashover model is incorporated into TWTDA. It becomes clear that the archorn voltages of the other two phases show a quite similar time-varying characteristic after one-phase back-flashover. An EMTP simulation is also carried out. The archorn voltages computed by the electromagnetic transients program (EMTP) agree well with those computed by TWTDA before the back-flashover on one phase. On the other hand, during about 1 [micro]s after the one-phase back-flashover, the archorn voltages of the other two phases computed by EMTP deviate much from those computed by TWTDA. Particularly in the case of the middle- or the lower-phase back-flashover, the deviation is noticeable. The reason for this discrepancy is discussed. Index Terms--Back-flashover, electromagnetic transients program (EMTP), lightning surge, numerical electromagnetic field analysis.