On Multiple-Resonator-based Implementation of IEC/IEEE Standard P-Class Compliant PMUs

Authors :
Kušljević, Miodrag D.
Tomić, Josif J.
Poljak, Predrag
Kušljević, Miodrag D.
Tomić, Josif J.
Poljak, Predrag
Source :
Energies
Publication Year :
2021

Abstract

This article deals with the implementation of the P-Class PMU compliant with IEC/IEEE Standard 60255-118-1:2018 by usage of a multiple-resonator (MR)-based approach for harmonic analysis having been proposed recently. In previously published articles, it has been shown that a trade-off between opposite requirements is possible by shifting a measurement time stamp along the filter window. Positioning the time stamp in a proximity of the time window center assures flat-top frequency responses. In this article, through simulation tests carried out under various conditions, it is shown that requirements of the IEC/IEEE Standard 60255-118-1:2018 can be satisfied by the second and third order MR structure for particular conditions of the time stamp location.