1. Arc Flash Calculations for a 1.3-MW Photovoltaic System.
- Author
-
Doan, Daniel R. and Derer, Richard M.
- Subjects
- *
FLASHOVER , *PHOTOVOLTAIC power generation , *PHOTOVOLTAIC effect , *OVERCURRENT protection , *INDUSTRIAL safety , *SHORT-circuit currents - Abstract
When planning for the installation of a 1.3-MW photovoltaic (PV) system and its integration into an existing facility's electrical system, an arc flash study was performed to determine the best protective device settings to minimize the arc flash energy in the PV system and to determine the effect of the additional short-circuit current on arc flash calculations for the existing system. The existing system has distribution at 13.8 kV and two 10-MVA transformers to a 2.4-kV feeder system. The PV system adds the hazard of 500-Vdc subarray collection wiring and terminations. The dc arc flash exposure of PV systems, including those in the inverter enclosures, can be complicated, and this paper outlines the basic data collected for the study, the steps taken to complete the calculations, the methodology used, the results, and the team's learnings. [ABSTRACT FROM AUTHOR]
- Published
- 2015
- Full Text
- View/download PDF